FE-13 Fire Suppression Systems

FE-13, the newest of the clean agents to emerge from NFPA 2001, is one of the safest clean agents now available. FE-13, DuPont's entry into the field, is UL listed and systems are currently available from Fireline and Kidde-Fenwal.

FE-13 (trifluromethane) is the safest of the three most commonly used clean agents (FE-13, FM-200 and Inergen). Systems are typically designed at 16-21% concentrations but FE-13 has no exposure restrictions until concentrations reach 30% or higher. The ability to design at higher than required concentrations makes FE-13 an ideal agent for occupied areas where very rapid extinguishment is desired.

Two other characteristics make this a unique agent that should be seriously considered for your clean agent requirements. First, nozzles can be located at heights of up to 25 feet as compared to only 12 feet for FM-200 systems. Second, due to its low boiling point, FE-13 can be used in temperatures as low as 40 degrees F.

As with other clean agents, FE-13 can be used in any area with high valued electronics such as computer facilities, battery rooms and telecommunications facilities. It also has many industrial applications including unheated storage areas.

Features

  • High Pressure Steel Cylinders
  • Agent storage to -40 degrees F.
  • Central storage manifolding
  • Partial fill of cylinders possible
  • Maximum nozzle coverage 30 ft. x 30 ft.
  • Maximum nozzle height 25 ft.

Fireline can design your FE-13 system for you. Our Engineering Department will perform all flow calculations, pipe layout, and nozzle selection. Engineered "E" size drawings will be prepared by level IV NICET certified design specialists. Complete submittal packages will be prepared within days of receiving your order for your FE-13 fire suppression system.