Gaseous agent special hazard suppression systems are most often designed and installed to protect industrial equipment, process equipment, flammable liquid areas,clean environments and electronic equipment with an extremely high asset value such as computer centers, data storage equipment, telecommunications equipment and other mission critical equipment. Often, clean agent systems are designed and installed to protect intangible assets, such as special software, down time, electronic transfer of assets and business interruption. It is imperative that these systems be installed and maintained in accordance with the guidelines of the National Fire Protection Association's pamphlets 12, 12A, 2001 and others. Fireline's NICET certified technicians inspect,test and maintain fire suppression systems in accordance with the NFPA code requirements and the requirements of the Authority Having Jurisdiction.
*Semi Annual Checklist
Room integrity visually inspected
Installation drawings match system
Power supply
Agent storage containers checked
Pressure checked
Ouantity of agent checked and recorded
Cylinders weighed (if necessary)
Cylinders secure
Hoses checked**
Piping and nozzles checked
Secure
Clean
Complete functional test
Audible devices tested
Shutdowns tested as needed
Dampers operable
Manual releases tested
Abort circuitry tested
Detectors checked and cleaned
Time delay checked
Control panel functioning
Annunciator functioning
Testing in accordance with NFPA 12, 1 1-) A, 2001
*High pressure hoses shaII be hydrostaticaIly tested every five years in accordance with the above noted NFPA codes